Ammonia plant-room automation

Plant
Food plant
Section
Central refrigeration plant room
Scope
Control logic design, program, failure analysis and on-site testing
  • 3.2MWplant cooling demand
  • 4compressors: three reciprocating, one screw
  • 3suction levels: −8, −4 and +3 °C
  • 6consumer circuits, each with its own pump
  • 9control-logic states (state machine)
  • 28failure modes in the FMEA
  • 5conditions in series; without them no machine runs

Brief

Automatic compressor control for a plant room with only occasional operator attendance, including machines standing in for each other when one fails.

The ammonia plant room as a schematic: four compressors, three piston and one screw, three suction levels at −8, −4 and +3 °C, and six consumer circuits, each with its own pump. The control system is cabled to the compressors’ control units and to the circuit pumps.−8 °C−4 °C+3 °C
Orange: the control system and its signals to the compressors’ control units and the circuit pumps.

Scope

Control logic as a state machine, program and HMI in TIA Portal, a written description and pseudocode, an FMEA failure analysis, a calculation of machine efficiency on the three levels, and on-site testing in the role of automation engineer.

Interfaces

A higher-level SIMATIC PLC, the compressors’ own control units, frequency converters, evaporator control valves, leak detection and emergency ventilation.

Platform

S7-1200, TIA Portal, FMEA. Every transition has its own commented network in the program.

Machine deployment logic

Self-evaluating logic in the PLC program decides how the compressors are deployed. If a machine fails, the suction levels can cover for each other.

Three suction levels at −8, −4 and +3 °C, with cross-connections between neighbouring levels.−8 °C−4 °C+3 °C
Suction levels and the cross-connections between them.

Safety and failure analysis

  • Two-step start. The suction valve opens first. The motor gets its command only once the valve position is confirmed, so a machine never starts against a closed suction.
  • Run conditions. Condensing pressure within the permitted window, NH₃ leak detection, emergency stop, fire and ventilation failure. Losing any one of them stops all four machines at once.
  • Emergency state. The machines stop, the suction valves close and emergency ventilation runs. The only way back is a manual reset after the operator has intervened.
  • Power failure. When power returns, the station does not start by itself. The operator has to set the run enable again.

The interlocks follow the requirements of EN 378-3.

State machine

The nine states of the control logic and the transitions between them, named as in the design.

  1. S0Init / Reset
    • to S1
  2. S1Standby
    • to S2
    • to S3
  3. S2Active −8 °C circuit
    • to S5
  4. S3Standalone
  5. S4Capacity boost
    • to S2
    • to S6
  6. S5Cross-connection
    • to S4
  7. S6COP optimisation
    • to S4
    • to S2
    • to S7
  8. S7Controlled shutdown
    • to S1
  9. S8Emergency / Fault
    • to S0

Only the main transitions are shown. An alarm leads from any state to S8 Emergency / Fault; the only way back is a manual operator reset (S8 → S0).

HMI

One screen for the whole plant room. Circuits, suction levels and machines are drawn as they are connected. Each machine shows its role and output. Run conditions are listed one by one.

The operator’s name is omitted. Values on the screens are illustrative.